Filter Backwash Recycling Rule Recordkeeping Form - Connecticut Department Of Public Health Page 2

Download a blank fillable Filter Backwash Recycling Rule Recordkeeping Form - Connecticut Department Of Public Health in PDF format just by clicking the "DOWNLOAD PDF" button.

Open the file in any PDF-viewing software. Adobe Reader or any alternative for Windows or MacOS are required to access and complete fillable content.

Complete Filter Backwash Recycling Rule Recordkeeping Form - Connecticut Department Of Public Health with your personal data - all interactive fields are highlighted in places where you should type, access drop-down lists or select multiple-choice options.

Some fillable PDF-files have the option of saving the completed form that contains your own data for later use or sending it out straight away.

ADVERTISEMENT

Instructions
1.
Note the operating period for the information provided.
2.
The frequency at which the recycle stream is returned can be described as
continuous, once a day, or as another frequency.
3.
Fill out all information for each of your filters. If some or all filters are operated the
same, note the appropriate filter numbers.
2
4.
The backwash flow is obtained by multiplying filter surface are (in ft
by backwash
2
rate (gpm/ft
). Use the average backwash rate to get the average flow and the
maximum backwash rate to get the maximum flow. If the flow is varied throughout
the backwash process, then the average can be computed on a time-weighted basis
as follows:
(Backwash Rate 1 X Duration 1) + (Backwash Rate 2 X Duration 2) +...
Duration 1 + Duration 2 + …
5.
The filter run length time is the sum of the time that the filter is producing water
between backwashes.
6.
Describe how run length time is determined. For example, is the run length based
on head loss across the filter, turbidity levels of filter effluent, a predetermined
amount of time, or another method?