PART III – NEW RESIDENT BOARD & CARE OCCUPANCIES
PREFIX
MET
K345
Fire Alarm System - Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved
program complying with the requirements of NFPA70, National Electric Code,
and NFPA 74, National Fire Alarm and Signaling Code. Records of the
system acceptance, maintenance and testing are readily available.
32.3.3.4.1, 9.6.1.3
K346
Fire Alarm System – Out of Service
Where a required fire alarm system is out of service for more than four hours
in a 24-hour period, the authority having jurisdiction shall be notified, and the
building shall be evacuated or an approved fire watch shall be provided for all
parties left unprotected by the shutdown until the fire alarm system has been
returned to service.
32.2.3.4.1, 9.6.1.3, 9.6.1.5, 9.6.1.6
K347
Smoke Alarms and Smoke Detection Systems
Approved smoke alarms shall be installed in accordance with 9.6.2.10 inside
every sleeping room, outside every sleeping area in the immediate vicinity of
the bedrooms and on all levels within a resident unit.
Corridor and spaces open to the corridors shall be provided with smoke
detectors complying with NFPA 72, and are arranged to initiate and alarm that
is audible in all sleeping areas.
Smoke detection systems shall not be required in unenclosed corridors,
passageways, balconies, colonnades, or other arrangements with one or
more sides along the long dimension fully or extensively open to the exterior
at all times.
32.3.3.4.7, 32.3.3.4.8.1, 32.3.3.4.8.3
K351
Sprinkler System – Installation
All buildings shall be protected throughout by an approved automatic sprinkler
system in accordance with Section 9.7.1.1(1) and provided with Quick-
response or residential sprinklers throughout.
32.3.3.5.1
K352
Sprinkler System - Supervisory Signals
Automatic sprinkler system shall be provided with electrical supervision in
accordance with 9.7.2.
32.3.3.5.5
Form CMS-2786W (10/2016)
Page 23