Sra Series Fan-Forced Wall Heaters Product Submittal Sheet Page 2

Download a blank fillable Sra Series Fan-Forced Wall Heaters Product Submittal Sheet in PDF format just by clicking the "DOWNLOAD PDF" button.

Open the file in any PDF-viewing software. Adobe Reader or any alternative for Windows or MacOS are required to access and complete fillable content.

Complete Sra Series Fan-Forced Wall Heaters Product Submittal Sheet with your personal data - all interactive fields are highlighted in places where you should type, access drop-down lists or select multiple-choice options.

Some fillable PDF-files have the option of saving the completed form that contains your own data for later use or sending it out straight away.

ADVERTISEMENT

Catalog Number
Volts
Amps
Watts
BTU/HR
Wire Size
SRA1012DSF
120
8.4/4.2
1000/500
3413/1706
14AWG
SRA1512DSF
120
12.5/6.3
1500/750
5120/2560
12AWG
SRA1812DSF
120
15.0/7.5
1800/900
6143/3072
12AWG
240
8.4/4.2
2000/1000
6826/3413
14AWG
SRA2024DSF
208
7.3/3.6
1500/750
5120/2560
14AWG
277
7.3/3.6
2000/1000
6826/3413
14AWG
SRA2027DSF
240
6.3/3.2
1500/750
5120/2560
14AWG
277
5.5/2.75
1500/750
5120/2560
14AWG
SRA1527DSF
240
4.7/2.4
1125/562
3840/1920
14AWG
SRA2020DSF
208
9.6/4.8
2000/1000
6826/3413
14AWG
Accessories
SRASM
Surface Mounting Frame (Accessory) Order Separately
12-1/2” (318mm)H X 10-3/8” (264mm)W X 4” (102mm) - Northern White
SRAS1
1” (25mm) Recess Mounting Frame (Accessory) Order Separately - Northern White
SRAS2
2” (50mm) Recess Mounting Frame (Accessory) Order Separately - Northern White
SRAFCTP
Tamper-resistant front cover - Northern White
ARCHITECT’S AND ENGINEER’S SPECIFICATIONS*
MOTOR AND CONTROLS: The fan motor shall be impedance
The heating equipment shall include an electric automatic
fan forced air heater suitable for small area heating, as
protected, permanently lubricated. Fan control shall be of
manufactured by Berko®, a Marley Engineered Products®
the bi-metallic, snap-action type and shall activate fan after
Brand, Bennettsville, SC. The heater shall be designed for wall
heating element reaches operating temperature, and continue
mounting, recess or surface. Heaters shall be cETLus listed.
to operate the fan after the thermostat is satisfied and until
all heated air has been discharged. The thermostat shall be
BACK BOX: The back box shall be designed as a recessed
single-pole type on all models. Thermal cutout shall be self-
rough-in box in either masonry or frame installations and is
hold (manual-reset) type designed to shut off heat in the event
also used when surface mounting frames are used in surface
of overheating. The fan shall be four-bladed aluminum. A back-
mounting installations. The back box shall be heavy gauge
up (End of Life) thermal fuse shall be provided for additional
galvanized steel and shall contain knockouts through which
safety.
power leads enter.
SURFACE MOUNTING FRAME: The surface mounting frame
INNER FRAME ASSEMBLY: The heater assembly, which fits
shall be of heavy gauge steel designed to mount around the
into the back box, shall consist of a heavy gauge steel fan
back box for a finished surface installation. Slot knock outs
panel to which all of the operational parts of the heater are
shall be provided for power supply conduit.
mounted. The inner frame assembly shall be completely pre-
wired.
FRONT COVER: The louvered front cover shall be of heavy
gauge steel with a powder paint finish. A plug button will be
HEATING ELEMENT: The heating element shall be of the
provided to replace the thermostat knob and render the unit
non-glowing design consisting of an 80/20 nickel-chromium
tamper-resistant.
resistance wire enclosed in a steel sheath to which plate fins
FINISH: All sheet metal parts, except the galvanized steel
are copper brazed. The element shall cover the entire air
discharge area to ensure uniform heating of all discharged air.
back box, shall be phosphatized, then completely painted by a
It shall be warrantied for 5 years.
powder paint process.
ON/OFF SWITCH: A double-pole, single throw on/off switch
*
In the interest of continual improvements in product and performance,
shall be mounted on the back box for positive disconnect of
Marley Engineered Products reserves the right to change specifications
power supply. It will be completely concealed behind the
without notice.
front cover.
ZSS-BSRAO | 9-2015