Application Form For Permit, Permit, And Certificate Of Completion For The Installation Or Alteration Of Fuel Oil Burning Equipment And The Storage Of Fuel Oil - Department Of Fire Services Page 2

ADVERTISEMENT

ALL INSTALLATIONS
Note To Installer: Inspections will be conducted using this
checklist as a guideline. Current regulations will apply.
UNENCLOSED TANKS
All applications must be on Form 1
Over 10,000 gallons on site requires License &
Permit from local community
Single tanks shall not be larger than 660 gallons
Certificate of Competency required, no other
Maximum aggregate capacity of unenclosed
license acceptable, plumbing, electrical, etc.
multiple tanks is 1320 gallons
Verify emergency shut-off is outside burner room
Unenclosed tanks shall be at least five feet from an
internal or external flame
Verify separate circuit for oil burner
Unenclosed tanks shall not obstruct service meters,
Verify presence of overhead thermal switch
service panels and shutoff valves
Verify presence of service switch within 3' of burner
Bottom outlet tanks pitched to the opening
Verify presence of high limit controller
Tanks exposed to vehicles will be protected by
Primary control has safety shutoff within 15 secs.
barriers
Stack type primary may be easily removed
Steam boiler equipped with low-water cut-off
ENCLOSED TANKS
Clear access to clean out and services panels
No oil leaks present at burner
Over 660 gallon tanks enclosed by two hour fire
resistive assembly
Installation instructions present on site
Tank enclosures provided with 6" high tight sills or
Combustion test results on Form 1
ramps
Three metal screws at each joint in chimney
Tank is 4" above floor supported by 12" thick
Thimble present at chimney connection
masonry saddles spaced not more than eight feet
on centers and 15" from top and walls of enclosure
IF POWER VENTER IS USED: Check air pressure
switch, post purge control and secondary control.
All oil must be transferred by pump, and
Installation instructions present.
connections must be at the top of the tank
Draft regulator is present unless exempted
Adequate air is present for combustion
ALL TANKS
Adequate clearances per manufacturers listing
Thermal valves at burner and tanks
Two tanks may be cross-connected as shown in
Fig. 4.03 1.
Listed flexible hose may be used.
Return lines must enter the top of tanks
No Teflon tape on oil line or on oil line fittings
Vent pipes must be two feet from building openings
No compression fittings are permitted
Vent pipes must terminate 3 ft. above grade min.
Solder joints made with 500 degree F solder or
greater
Vent pipes must have weatherproof caps
All oil supply and return lines must be protected
Fill pipes must be two feet from building openings
from injury. All new lines must be continuously
Fill pipes must have tamper proof identifying caps
sleeved with non metallic tubing. Oil safety valves
may be used on existing lines not exposed to
IF POWER VENTER IS USED:
freezing. Overhead lines require no sleeve and are
All outside connections sealed Vent terminal must be three
permitted
feet above all air inlets within 10ft. Burner air intake is
Oil supply lines and return lines to tanks exposed to
exempted Vent terminal must be four feet from doors and
freezing temperatures must come off the top of
windows. Vent must be one foot above finished grade. Three
tanks
foot clearance from inside corners. Not above or within three
Lines for kerosene, and range oil (#1) are exempt -
feet of an oil tank. Seven feet above a public walkway.
No oil leaks present at tank
Listed oil filter is present
Tank is UL80 or (DIB+) PV-VI 321 (under 660 gal)
OUTSIDE TANKS
or UL 142 (over 600 gal)
Shutoff valve located at bottom of tank
All UST's and tanks over 660 gallons must be
Size of vent as per manufacturer
installed as per NFPA 31
Oil tank gauge must be present to determine oil
Tank protected from physical damage
level
Tanks exterior coated with organic alkyd resin or
Inside tanks have audible fill device (vent alarm)
asphalt paint
Outlet cross connection at bottom of tanks must be
Damaged protective coatings must be recovered
3/8" pipe or tubing.
Tank does not block means of egress
Non-combustible tank supports, tank
secure.
Tank mounted on continuous 4" thick slab that
extends 8" beyond tank perimeter
Tank is supported by rigid non-combustible
supports

ADVERTISEMENT

00 votes

Related Articles

Related forms

Related Categories

Parent category: Legal
Go
Page of 2