Name of Facility
2012 LIFE SAFETY CODE
ID
NOT
MET
N/A
REMARKS
PREFIX
MET
K222
☐ DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance
with 7.2.1.6.1 shall be permitted on door assemblies serving low and
ordinary hazard contents in buildings protected throughout by an approved,
supervised automatic fire detection system or an approved, supervised
automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
☐ ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with
7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
☐ ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall
be permitted on door assemblies in buildings protected throughout by an
approved, supervised automatic fire detection system and an approved,
supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
K223
Doors with Self-Closing Devices
Doors in an exit passageway, stairway enclosure, or horizontal exit, smoke
barrier, or hazardous area enclosure are self-closing and kept in the closed
position, unless held open by a release device complying with 7.2.1.8.2 that
automatically closes all such doors throughout the smoke compartment or
entire facility upon activation of:
Required manual fire alarm system; and
Local smoke detectors designed to detect smoke passing through the
opening or a required smoke detection system; and
Automatic sprinkler system, if installed; and
Loss of power.
18.2.2.2.7, 18.2.2.2.8, 19.2.2.2.7, 19.2.2.2.8
Form CMS-2786R (10/2016)