Fire Safety Log Book Page 3

ADVERTISEMENT

Section 1: Advice on Testing and Maintenance
Records should be kept of all testing, maintenance and staff training to enable the responsible person to
demonstrate they have taken all reasonable steps to maintain adequate fire safety standards.
Fire Alarm
The alarm should be tested weekly by a competent person. A different call point should be tested each week using a
purpose made test key. Faults should be reported to someone who can authorise repairs. If the system cannot be
repaired immediately a risk assessment should be undertaken to ensure the area can continue to be safely used. The
person carrying out the risk assessment must be competent.
The system should be serviced by suitably qualified persons every six months or as agreed by the installers. Further
advice can be gained from BS 5839 Pt 1 2002.
Single Point detectors
Single point detectors must be tested weekly by operating the push button on the detector. Batteries on some models
should be tested weekly and on others every ten years. Some detectors do not allow for batteries to be replaced. Read
manufactures instructions.
Magnetically Hold Open Devices
Devices should be tested weekly along with the Fire Alarm to ensure they release and the fire door closes onto the latch
and to check the door has not warped. Where possible doors should be released during the night to release the strain on
the self closing device and door.
Magnetically or Electronically Secured Final Exits
Final exits locked by magnetic or electronic gate must be checked weekly to ensure they release on activation of the
Fire Alarm. All doors so secured should have a green call point fitted adjacent to the door on the inside face to give a
local release. In certain circumstances (to protect people) it may be necessary to vary away from this guidance. This can
only be agreed following a Fire Risk Assessment.
Emergency Lighting
The emergency lighting should be checked monthly by a competent person to ensure it functions correctly. This may be
carried out by purpose made test switches that will require a specific key or by isolating the local lighting sub-circuit. It is
important the lighting works when the local lighting circuit fails and does not rely on the failure of the overall circuit.
The system should be serviced annually by suitably qualified engineers.
Further advice can be gained from
BS 5266 Pt 1.
Staff Training
All staff must receive training in what to do in the event of discovering a fire or hearing the alarm. This training should be
given by a competent person and take place as soon as possible after employment. Staff should receive refresher
training periodically. Some staff should be given instruction in the use of fire fighting equipment. Some staff may require
additional training in Fire Warden duties if appropriate or in assisting persons with disabilities. Further guidance with
regard to the premises needs can be found in the Fire Risk Assessment.
Evacuation Drill
Normal commercial premises staff should complete an evacuation drill once every 12 months. Care homes staff should
complete an evacuation drill once every six months.
Fire Fighting Equipment
Fire fighting equipment should be hung on purpose made brackets approximately 1 metre off the floor or sat in purpose
made floor holders. The equipment should be checked weekly to ensure it is in position and appears undamaged.
The equipment should be serviced annually by a competent person. Further advice can be gained from BS 5306.
Fire Doors
Designated Fire Doors should be checked quarterly to ensure it self closes onto the latch, the smoke seal is in good
condition and touches the frame. The door should sit square in the frame and have signage stating “Fire Door – Keep
Shut” (not bedroom doors in HMO).
Firesafe Solutions (UK) Ltd
Claylands Road
Bishops Waltham
Southampton
SO32 1BH
Telephone: 0845 456 5121
Fax: 01489 808930
e-mail: info@firesafesolutions.co.uk
2

ADVERTISEMENT

00 votes

Related Articles

Related forms

Related Categories

Parent category: Miscellaneous