New Orleans Fire Department
Mobile/Temporary Vendor Permit Requirements
***(For Official Use Only)***
Circle Appropriate. Answer
1.
Ves / No / N_A
A portable fire extinguishers shall be provided with a minimum rating of 2A10BC. (AM portable fire
extinguishers shall be visible and readily accessible) IFC906
2.
_Ves / No / NA
If portable generators are used, a portable fire extinguisher shall be provided with a minimum rating of
3A40BC. (This is in addition to any other required fire extinguishers). IFC906
3.
Yes I No / NA
All portable fire extinguishers must be properly tagged by a LA State Fire Marshal Licensed Extinguisher
Company. IFC906
4.
Yes / No / NA
A hood suppression system shall be installed when cooking operations produce any grease laden vapors
(pan frying, deep frying, griddle, etc.) IFC308.7
5.
Vcs / No / NA
All hood suppression systems shall be properly tagged by a LA State Fire Marshal Licensed Extinguisher
Company. IFC906.2.1
6.
Yes / No / NA
A Class K portable fire extinguisher shall be provided when cooking operations produce any grease laden
vapors. IFC906.2.1
7.
Yes / No / NA
Cooking appliances under hood suppression system shall not extend beyond the outer lip of the hood.
NFPA96
8.
Yes / No / NA
A minimum distance of 16 horizontal inches or 8 inch high baffle (on highest level) shall be maintained
between fryer surface and flame appliance. NFPA96
9.
Ves / No / NA
All LPG tanks shall be properly secured and located on the exterior of the mobile unit or in approved
location inside vending structures. NFPA54.NFPA58, IFC38
10.
Yes / No / NA
All LPG tanks shall be properly labeled "LPG" or "Liquefied Petroleum Gas". NFPA54, NFPA58,IFC38
' 1 •
Ves / No / NA
All LPG tank and appliance fuel lines/hoses shall be properly labeled "LPG" or "Liquefied Petroleum
Gas". NFPA54, NFPA58JFC38
12.
Yes / No / NA
All LPG tanks shall be equipped with pressure relief devices,
NFPA54,NFPA58,IFC38
13.
Yes / No / NA
All LPG tanks shall be equipped with an approved gas regulator device. NFPA54,NFPA58,IFC38
14.
Yes / No / NA
All cooking operation fuel supply lines shall have an approved gas shut off valve installed on the interior
and exterior of the mobile unit or structure, (interior-before appliances / exterior-near tank)
NFPA54,NFPA58,IFC38, IFC102
15.
Yes / No / NA
"NO SMOKING" signs shall be conspicuously posted next to LPG tank locations. 1FC38
16.
Yes_/ N o / N A
A 15 feet clearance shall be maintained on each side of any fire hydrant. 1BC912.6.3
17.
Yes / N o /JSA
All cooking appliances shall have an on/off control and/or an adjustable heating control device. NFPA96
18.
Yes / N p / N A
All cooking appliances are at least 3 feet from any combustibles.
19.
Yes / No_/ flj A
All non-cooking heating equipment shall be of an approved type (UL or FM) and place at least 3 feet from
any combustible materials. 1FC605.10.4
20.
Ygs /_No_/_NA
All fabrics, membranes, tarps, canopies, and tents shall be flame resistant (Flame Certificated must be
submitted). IFC24.04