Sprinkler Plan Review Checklist
Job Number
11. Hydraulic Calculations
12. General Notes and Information on Plans
a. Hydraulic reference points indicated
a. All material and installation to conform to the
b. Source pressure indicated
standards of NFPA-13D
c. Demand pressure indicated
b. Sprinkler heads omitted from bathrooms due
to non-combustible fixtures and less than 55
d. 10% safety margin
square feet
e. Source elevation indicated
c. Waterflow alarm(s) shall be clearly audible in
all living spaces over background noise with all
f. Proper sprinkler data used
intervening doors closed
1) Minimum flow for spacing
d. Exterior exposed steel piping painted
2) Accurate K-factor
e. Storage in attic is not allowed and sprinkler
heads have not been provided in these areas
g. Domestic demand added (if required)
f. Access to areas under enclosed stairwells has
h. Meter loss (chart) or (NFPA-13D)
not been provided and sprinklers have not been
provided for these areas
I. Fixed loss device (backflow)
g. All penetrations through firewalls such as walls
j. Single most hydraulically demanding sprinkler
and ceilings between attached garage and
(if required)
residence will be sealed in an approved manner
to maintain the integrity of the firewall.
k. Most hydraulically demanding multiple
sprinklers (2-3-4)
h. Pipe hangers shall be in accordance with
NFPA-13D and the written instructions of the
l. Elevation at remote heads
pipe manufacturer
m. Loss through tees on run calculated
I. Drilling or notching of structural members
shall be performed in strict accordance with
current IBC
j. Three sprinklers of each type used PLUS
wrench in cabinet
Comments: