Form Cms-2786x - Fire Safety Survey Report - Icf-Iid (Apartment House) 2012 Life Safety Code Page 13

ADVERTISEMENT

 
 
Name of Facility
2012 LIFE SAFETY CODE
PART II – EXISTING APARTMENT HOUSE
MET
NOT
N/A
REMARKS
ID
MET
PREFIX
(PROMPT OR SLOW EVACUATION)
K354
Sprinkler System - Out of Service
Where a required automatic sprinkler system is out of service for more
than four hours in a 24-hour period, the authority having jurisdiction shall
be notified, and the building shall be evacuated, or an approved fire watch
system be provided for all parties left unprotected by the shutdown until the
sprinkler system has been returned to service.
9.7.6.1
K355
Portable Fire Extinguishers
Portable fire extinguishers shall be provided in hazardous areas in
accordance with Section 9.7.4.1 unless the building is provided with an
approved supervised automatic sprinkler system.
30.3.5.7
K362
Corridors - Construction of Walls
Exit access corridor walls shall consist of fire barriers in accordance with
8.3 having a minimum ½ hour FRR.
31.3.6.1*
K363
Corridor – Doors
Doors that open onto exit access corridors other than those complying with
8.3.4 shall have not less than a 20 minute fire protection rating in
accordance with 8.3. In buildings using Options 3 or 4, doors shall be
constructed to resist the passage of smoke.
Doors that open onto exit access corridors shall be self-closing and self-
latching.
31.3.6.2.1, 31.3.6.2.2, 31.3.6.2.3
K364
Corridor – Openings
Unprotected openings shall be prohibited in exit access corridor walls and
doors.
Spaces shall be permitted to be unlimited in area and open to the corridor
provided that all of the following criteria are met:
1. The space is not used for guest rooms, guest suites or hazard areas.
2. The building is protected throughout by an approved, supervised
automatic sprinkler system.
3. The space does not obstruct access to required exits.
Transoms, louvers, or transfer grills shall be prohibited in walls or doors of
exit access corridors.
31.3.6.3.1, 31.3.6.3.2, 31.3.6.4