Name of Facility
2012 LIFE SAFETY CODE
ID
MET
NOT
N/A
REMARKS
PART III – NEW APARTMENT HOUSE
MET
PREFIX
K342
Fire Alarm System – Initiation
Initiation of the required fire alarm system shall be by manual means in
accordance with 9.6.2. Initiation of the required fire alarm system by
manual means shall not be required in buildings four or fewer stories in
height, containing not more than 16 dwelling units, protected throughout by
an approved, supervised automatic sprinkler system installed in
accordance with 30.3.5.1.
In buildings protected throughout by an approved automatic sprinkler
system, the required fire alarm system shall be initiated upon operation of
the automatic sprinkler system.
30.3.4.2.1, 30.3.4.2.2, 30.3.4.3.3
K343
Fire Alarm System – Notification
Occupant notification shall be provided automatically in accordance with
section 9.6, and both of the following shall also apply:
1. Visible signals shall be installed in units designed for the hearing
impaired.
2. Positive alarm sequence in accordance with 9.6.3.4 shall be permitted.
Annunciation, and annunciation zoning, in accordance with 9.6.7 shall be
provided except as noted below:
1. Annunciation and annunciation zoning shall not be required in
buildings two or fewer stories in height and having not more than 50
dwelling units.
2. Annunciation and annunciation zoning shall not be required in
buildings four or fewer stories in height containing not more than 16
dwelling units and protected throughout by an approved, supervised
automatic sprinkler system.
Fire department notification shall be accomplished in accordance with
9.6.4.
30.3.4.3.1 through 30.3.4.3.5
K345
Fire Alarm System – Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an
approved program complying with the requirements of NFPA 70, National
Electric Code, and NFPA 74, National Fire Alarm and Signaling Code.
Records of the system acceptance, maintenance and testing are readily
available.
30.3.5.1, 9.6.1.3