PART III – NEW APARTMENT HOUSE
MET
PREFIX
K347
Carbon monoxide alarms or carbon monoxide detectors shall be provided
in areas other than dwelling units in accordance with 9.8 as modified
below:
They shall be installed in accordance with the manufacture’s published
instructions in the following specified locations:
1. On the ceilings of rooms containing permanently installed fuel-burning
appliances.
2. Centrally located within occupiable spaces served by the first supply
air register from a permanently installed fuel burning HVAC system.
3. Centrally located within occupiable spaces adjacent to a
communicating attached garage.
30.3.4.6.1 through 30.3.4.6.5
K351
Sprinkler System Installation
All buildings shall be protected throughout by an approved, supervised
automatic sprinkler system installed in accordance with 30.3.5.2.
Where an automatic sprinkler system is installed for total or partial building
coverage, the system shall be in accordance with Section 9.7 as modified
by 1 and 2 below. In buildings not more than four stories above grade
plane, a sprinkler system complying with NFPA 13R shall be permitted.
1. In buildings sprinklered in accordance with NFPA 13, closets less than
12 square feet in area. In individual dwelling units, sprinklers shall not
be required to be sprinklered. Closets that contain equipment such as
washers, dryers, furnaces, or water heaters shall be sprinklered
regardless of size.
2. The draft stop and closely spaced sprinkler requirements shall not be
required for convenience openings complying with 8.6.9.1 where the
convenience opening is within the dwelling unit.
Listed quick-response or listed residential sprinklers shall be used
throughout all dwelling units.
Open parking structures complying with NFPA 88A, Standard for Parking
Structures, that are contiguous with apartment buildings shall be exempt
from the sprinkler requirement.
Buildings with unprotected openings in accordance with 8.6.6 shall be
protected throughout by an approved, supervised automatic sprinkler
system.
30.3.5.1, 303.5.2, 30.3.5.3* 30.3.5.4, 30.3.5.5 30.3.5.6, 30.3.5.7