Name of Facility
2012 LIFE SAFETY CODE
ID
MET
NOT
N/A
REMARKS
PART III – NEW APARTMENT HOUSE
MET
PREFIX
K231
Means of Egress Capacity
Capacity of means of egress shall be in accordance with Section 7.3.
Street floor exits shall be sufficient for the occupant load of the street floor
plus the required capacity of stairs and ramps discharging onto the street
floor.
Corridors with a required capacity of more than 50 persons, defined in
Section 7.3, shall be of sufficient width to accommodate the required
occupant load but have a width of not less than 44 inches.
Corridors with a required capacity of not more than 50 persons as defined
in 7.3, shall be not less than 36 inches in width.
30.2.3.1 through 30.2.3.4
K241
Number of Exits - Story and Compartment
The requirements of 30.2 shall apply only to the parts of means of egress
serving the apartment(s) used as a residential board and care occupancy.
However, if a new board and care occupancy is created in an existing
apartment building, the existing requirements found in Section 30.2 shall
apply to the parts of the means of egress serving the apartment(s) used as
a residential board and care occupancy.
Every dwelling unit shall have access to not less than two separate exits
remotely located from each other as required by 7.5.1.
Dwelling units meeting the conditions of 30.2.4.4 are permitted to have
single exit access.
Buildings having not more than four stories may have a single exit
provided all the conditions of 30.2.4.6 are met.
32.4.2.1, 32.4.2.2, 30.2.4.3, 30.2.4.4, 30.2.4.6
Form CMS-2786X (10/2016)
Page 19