Name of Facility
2012 LIFE SAFETY CODE
ID
NOT
MET
N/A
REMARKS
PREFIX
MET
2012 NEW
K311
Vertical openings shall be enclosed or protected per 8.6, unless one of the
following conditions exist:
1. Unenclosed vertical openings per 8.6.9.1 are permitted.
2. Exit access stairs may be unenclosed if they meet the 2 conditions:
a. Building is sprinkler protected throughout.
b. Total travel distance to outside does not exceed 100 feet.
Floors that are below the street level and are used for storage or any use
other than a business occupancy, shall not have any unprotected openings
to the business occupancy floors.
20.3.1, 38.3.1.1, 38.3.1.2
Hazardous Areas – Enclosure
K321
Hazardous areas must meet one of the following:
Contain 1 hour rated enclosure when non-sprinklered
Sprinkler protected with smoke resistive separation
Severe Hazard locations contain sprinkler protection and 1 hour
separation with 3/4 hour rated self-closing doors
20.3.2, 21.3.2, 38.3.2, 38.3.2.2, 39.3.2.1, 39.3.2.2, 8.7
Laboratories
K322
Laboratories employing quantities of flammable, combustible, or hazardous
materials that are considered a severe hazard are protected by 1-hour fire
resistance-rated separation, automatic sprinkler system, and are in
accordance with 8.7 and with NFPA 99.
Laboratories not considered a severe hazard are protected as hazardous
areas (see K321).
Laboratories using chemicals are in accordance with NFPA 45.
Gas appliances are of appropriate design and installed in accordance with
NFPA 54. Shutoff valves are marked to identify material they control.
Devices requiring medical grade oxygen from the piped distribution system
meet the requirements under 11.4.2.2 (NFPA 99).
20.3.2.2, 21.3.2.2
9.3.1.2, 11.4.3.2, 15.4 (NFPA 99)