Name of Facility
2012 LIFE SAFETY CODE
ID
NOT
MET
N/A
REMARKS
PREFIX
MET
2012 NEW
K251
Dead-end corridors are no more than 50 feet in sprinklered buildings, and
no more than 20 feet in non-sprinklered buildings.
Common path of travel is no more 75 feet, and no more than 100 feet in
sprinklered buildings or single tenant space with an occupant load not
exceeding 30 persons.
20.2.5, 38.2.5.2, 38.2.5.3
Travel Distance to Exits
K261
Travel distance between any point in a room and an exit is
not more than
150 feet or 200 feet in sprinklered buildings.
20.2.6, 21.2.6
Discharge from Exits
K271
Exit discharge is arranged in accordance with 7.7, provides a level walking
surface meeting the provisions of 7.1.7 with respect to changes in elevation
and shall be maintained free of obstructions. Additionally, the exit discharge
shall be a hard packed all-weather travel surface in accordance with CMS
Survey and Certification Letter 05-38.
20.2.7, 21.2.7, 38.2.7, 39.2.7, 7.7
Illumination of Means of Egress
K281
Illumination of means of egress, including exit discharge, is arranged in
accordance with 7.8 and shall be either continuously in operation or
capable of automatic operation without manual intervention.
20.2.8, 21.2.8, 7.8
Emergency Lighting
K291
Emergency lighting of at
least 1-1/2 hour duration is provided automatically
in accordance with 7.9.
20.2.9.1, 21.2.9.1, 7.9
Life Support Means of Egress
K292
2012 NEW (INDICATE N/A FOR EXISTING)
Where general anesthesia or life-support equipment is used, each
ambulatory health care facility shall be provided with an essential electric
system in accordance with NFPA 99.
(Indicate N/A if life support equipment is for emergency purposes only.)
20.2.9.2
Form CMS-2786U (10/2016)
Page 8