Name of Facility
2012 LIFE SAFETY CODE
ID
NOT
MET
N/A
REMARKS
PREFIX
MET
Rubbish Chutes, Incinerators, and Laundry Chutes
K541
2012 EXISTING
Rubbish chutes are installed per section 9.5:
Walls, partitions, and inlet openings meet the requirements of 8.3.
Doors of chutes open to a room designed exclusively for accessing the
chute opening.
Room used for accessing the chute opening(s) are separated from other
spaces per 8.7.
Chutes shall be permitted to open into rooms not exceeding 400 cubic
feet in size if the room is sprinkler protected and the room is not used for
storage.
OR
Existing installations having properly enclosed and maintained chute
openings shall be permitted to have inlets open to a corridor or normally
occupied space.
21.5.4, 9.5, NFPA 82
2012 NEW
Rubbish chutes are installed per section 9.5:
Walls, partitions, and inlet openings meet the requirements of 8.3.
Doors of chutes open to a room designed exclusively for accessing the
chute opening.
Room used for accessing the chute opening(s) are separated from other
spaces per 8.7.
Chutes shall be permitted to open into rooms not exceeding 400 cubic
feet in size if the room is sprinkler protected and the room is not used for
storage.
Maintenance and installation are per NFPA 82.
20.5.4, 9.5, NFPA 82
Form CMS-2786U (10/2016)