Name of Facility
2012 LIFE SAFETY CODE
ID
NOT
MET
N/A
REMARKS
PREFIX
MET
Alcohol Based Hand Rub Dispenser (ABHR)
K325
ABHRs are protected in accordance with 8.7.3.1, unless all conditions are
met:
•
Corridor is at least 6 feet wide.
•
Maximum individual dispenser capacity is 0.32 gallons (0.53 gallons in
suites) of fluid and 18 ounces of Level 1 aerosols.
•
Dispensers shall have a minimum of 4-foot horizontal spacing.
•
Not more than an aggregate of 10 gallons of fluid or 1135 ounces of
aerosol are used in a single smoke compartment outside a storage
cabinet, excluding one individual dispenser per room.
•
Storage in a single smoke compartment greater than 5 gallons complies
with NFPA 30.
•
Dispensers are not installed within 1 inch of an ignition source.
•
If floor is carpeted, the building is fully sprinkler protected.
•
ABHR does not exceed 95% alcohol.
•
Operation of the dispenser shall comply with Section 18.3.2.6(11) or
19.3.2.6(11).
•
ABHR is protected against inappropriate access.
20.3.2.6, 21.3.2.6, 8.7.3.1, CFR 416.44
Interior Wall and Ceiling Finish
K331
Interior wall and ceiling finishes in exits and exit access corridors shall have
a flame spread rating of Class A or Class B. The reduction in class of
interior finish for a sprinkler system as prescribed in 10.2.8.1 is permitted.
All other areas may be class C rated material.
Indicate flame spread rating(s) walls. _____________________
20.3.3, 21.3.3, 38.3.3, 39.3.3, 10.2
Interior Floor Finish
K332
2012 NEW (Indicate N/A for 2012 EXISTING)
Interior floor finish in exit enclosures must meet 10.2 and be Class I or
Class II. All other areas must meet 10.2.7.1 or 10.2.7.2.
Indicate rating(s) for floors_____________________
20.3.3, 21.3.3, 38.3.3, 39.3.3, 10.2
Form CMS-2786U (10/2016)
Page 13