Form Cms-2786u - Fire Safety Survey Report - Asc & Esrd 2012 Life Safety Code Page 7

ADVERTISEMENT

Name of Facility
2012 LIFE SAFETY CODE
ID
NOT
MET
N/A
REMARKS
PREFIX
MET
Number of Exits – Story and Compartment
K241
2012 EXISTING
Single means of egress is allowed from a mezzanine or balcony if one of
the following exist:
1. Common path of travel is under 100 feet if in a sprinklered building.
2. Common path of travel 75 feet if in a non-sprinklered building.
3. Common path of travel is not limited if occupant load is under 30.
Not less than 2 exits, as described in 38.2.2, are remotely located for each
fire section or patient care area of the building and are accessible from
each smoke compartment.
Patient care suites larger than 2500 square feet have 2 exits remotely
located from each other.
Egress from smoke compartments, if installed, shall be permitted through
adjacent compartments provided the egress does not return through the
compartment of fire origin.
21.2.3.1 through 21.2.3.5, 7.4.1.1, 7.4.1.3 through 7.4.1.6
2012 NEW
Meets the requirements of section 7.4.
Not less than 2 exits, as described in 38.2.2, are remotely located for each
fire section or patient care area of the building and are accessible from
each smoke compartment.
Patient care suites larger than 2500 square feet have 2 exits remotely
located from each other.
Egress from smoke compartments, if installed, shall be permitted through
adjacent compartments provided the egress does not return through the
compartment of fire origin.
20.2.4.1 through 20.2.4.5, 7.4
Dead-End Corridors and Common Path of Travel
K251
2012 EXISTING
Dead end corridors shall not exceed 50 feet.
Common path of travel is no more 75 feet, and no more than 100 feet
on a
sprinklered story. Common path of travel is not limited in single tenant
space with an occupant load not exceeding 30 persons.
21.2.5, 39.2.5.2
Form CMS-2786U (10/2016)
Page 7