Name of Facility
2012 LIFE SAFE TY CODE
ID
NOT
MET
N/A
REMARKS
PREFIX
MET
Multiple Occupancies – Sections of Ambulatory Health Care Facilities
K131
Multiple occupancies shall be in accordance with 6.1.14.
Sections of ambulatory health care facilities shall be permitted to be
classified as other occupancies, provided they meet both of the following:
The occupancy is not intended to serve ambulatory health care
occupants for treatment or customary access
They are separated from the ambulatory health care occupancy by a 1
hour fire resistance rating
Ambulatory health care facilities shall be separated from other tenants and
occupancies and shall meet all of the following:
Walls have not less than 1 hour fire resistance rating and extend from
floor slab to roof slab
Doors are constructed of not less than 1-3/4 inches thick, solid-bonded
wood core or equivalent and is equipped with positive latches.
Doors are self-closing and are kept in the closed position, except when
in use.
Windows in the barriers are of fixed fire window assemblies per 8.3.
Per regulation, ASCs are classified as Ambulatory Health Care
Occupancies, regardless of the number of patients served.
20.1.3.2, 21.1.3.3, 20.3.7.1, 21.3.7.1,42 CFR 416.44