SAMPLE DESIGN CALCULATIONS
APPENDIX
EXAMPLE C5. NEW FOUNDATION WALL DESIGN (continued)
Where P is equal to the average weight of the 30 ft long framed wall with gable end wall above. So,
 
2,924 kips- in .
2
2
V
= 4.0 -1.75
  (
1 1
20 in . )
2,000 lb/ in . + 0.25 (5, 670 lbs)
m
( 
19.1 kips)(360 in .
)
 
=
• Finding the resulting shear force per ACI-530-08 Equation 3-23:
which is acceptable
The resulting shear force per ACI 530-08 Equation 2-25 is:
(
)
• Determining the nominal shear strength and comparing to the in-plane shear capacity
Nominal Shear Strength
63.9 kips > 53.2 kips OK #4 @ 48 in. o.c. in-plane shear
• Investigate long (60 ft) wall for out-of-plane bending because axial load is also supported by
this wall. Neglect impact load in this analysis.
Treat wall as simple T-beam 4 ft wide and calculate axial pressure per load determined in Example
C4. Section Properties ACI 580-08 Section 1.9 and
h
≤ 9
9 h/r ≤ 99 h/r = 120/2.16 = 55.6 < 99
for
r
OK
where: h =
C-23
ENGINEERING PRINCIPLES AND PRACTICES for Retrofitting Flood-Prone Residential Structures