2012 LIFE SAFETY CODE
PART II – EXISTING RESIDENT BOARD & CARE OCCUPANCIES
MET
NOT
N/A
REMARKS
ID
MET
PREFIX
(PROMPT EVACUATION)
K321
Hazardous Areas – Enclosure
Any hazardous area that is on the same floor as, and is in or abut, a
primary means of escape or a sleeping room shall be protected by one of
the following means:
1.
Protection shall be an enclosure with a fire resistance rating of not
less than 1 hour, with a self-closing or automatic closing fire door in
accordance with 7.2.1.8 that has a fire protection rating of not less
than 3/4 hour.
2.
Protection shall be automatic sprinkler protection, in accordance with
33.2.3.5, and a smoke partition, in accordance with 8.4 located
between the hazardous area and the sleeping area or primary escape
route. Any doors in such separation shall be self-closing or automatic
closing in accordance with 7.2.1.8.
Other hazardous areas shall be protected in accordance with
33.2.3.2.5 by one of the following:
1. An enclosure having a fire resistance rating of not less than 1/2 hour,
with a self-closing or automatic-closing door in accordance with 7.2.1.8
that is equivalent to not less than a 1-3/4 inch (4.4 cm) thick, solid-
bonded wood core construction.
2. Automatic sprinkler protection in accordance with 33.2.3.5, regardless
of enclosure.
Areas with approved, properly installed and maintained furnaces and
heating equipment, and cooking and laundry facilities are not classified as
hazardous areas solely on basis of such equipment.
Standard response sprinklers shall be permitted for use in hazardous areas in
accordance with 33.2.3.2.
33.2.2.2.4, 33.2.3.2, 33.2.3.2.5
K331
Interior Wall and Ceiling Finish
Interior wall and ceiling finish in accordance with section 10.2. In
Prompt Evacuation Capability facilities, Class A, Class B, or Class C is
permitted. There are no requirements for interior floor finish.
33.2.3.3, 33.2.3.3.3