PART V – OPERATING FEATURES
ID
NOT
MET
N/A
REMARKS
PREFIX
MET
(New and Existing Facilities)
K752
Upholstered Furniture and Mattresses
New upholstered furniture within board and care facilities shall be tested
in accordance with the provisions of 10.3.2.1(1) and 10.3.3.
Upholstered furniture belonging to the resident(s) in sleeping rooms shall
not be required to be tested, provided that a smoke alarm is installed in
such rooms. Battery-powered single-station smoke alarms shall be
permitted.
Newly introduced mattresses shall be tested in accordance with the
provisions of 10.3.2.2 and 10.3.4.
Mattresses belonging to the resident(s) in sleeping rooms shall not be
required to be tested, provided that a smoke alarm is installed in such
rooms. Battery-powered single-station smoke alarms shall be permitted.
32.7.5.2.1, 32.7.5.3.2, 33.7.5.2.2, 33.7.5.3.1, 33.7.5.2.1, 33.7.5.2.2,
33.7.5.3.1, 33.7.5.3.2
K761
Staff
Staff shall be on duty in the facility at all times when residents requiring
evacuation assistance are present.
32.7.6, 33.7.6
Form CMS-2786V (10/2016)
Page
40