Name of Facility
2012 LIFE SAFETY CODE
PART II – EXISTING RESIDENT BOARD & CARE OCCUPANCIES
MET
NOT
N/A
REMARKS
ID
MET
PREFIX
(PROMPT EVACUATION)
K341
Fire Alarm System – Installation
A manual fire alarm system shall be provided in accordance with
Section 9.6, unless smoke alarms are interconnected and comply with
33.2.3.4.3 and there is not less than one manual fire alarm box per
floor arranged to continuously sound the required smoke alarms.
33.2.3.4.1, 33.2.3.4.1.1, 33.2.3.4.1.2
K343
Fire Alarm – Notification
Occupant notification is provided automatically in accordance with 9.6.3 by
audible and visual signals.
33.2.3.4.2, 9.6.3
K345
Fire Alarm System – Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved
program complying with the requirements of NFPA 70, National Electric
Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of
system acceptance, maintenance and testing are readily available.
9.7.5, 9.7.7, 9.7.8, and NFPA 25
K346
Fire Alarm System – Out of Service
Where a required fire alarm system is out of service for more than four hours
in a 24-hour period, the authority having jurisdiction shall be notified, and the
building shall be evacuated or an approved fire watch shall be provided for all
parties left unprotected by the shutdown until the fire alarm system has been
returned to service.
33.2.3.4.1, 9.6.1.3, 9.6.1.5, 9.6.1.6