Name of Facility
2012 LIFE SAFETY CODE
PART II – EXISTING RESIDENT BOARD & CARE OCCUPANCIES
NOT
ID
MET
N/A
REMARKS
MET
PREFIX
(SLOW EVACUATION)
MEANS OF ESCAPE REQUIREMENTS
K228
Stairways and Smokeproof Enclosures
In Slow Evacuation Capability facilities, stair enclosures shall not be
required in buildings of three or fewer stories protected throughout by an
approved automatic sprinkler system in accordance with 33.2.3.5 that uses
quick response or residential sprinklers. This exception shall be permitted
only if a primary means of escape from each sleeping area still exists that
does not pass through a portion of a lower floor, unless that route is
separated from all spaces on that floor by construction having a 1/2-hour fire
resistance rating.
In Slow Evacuation Capability facilities, of three or fewer stories protected
by an approved automatic sprinkler system in accordance with 33.2.3.5
stairs shall be permitted to be open at the topmost story only. The entire
primary means of escape of which the stairs are a part shall be separated
from all portions of lower stories.
33.2.2.4.6, 33.2.2.4.9
K258
Number of Exits – Patient Sleeping and Non-Sleeping Rooms
In Slow Evacuation Capability facilities, the primary means of escape for
each sleeping room shall not be exposed to living areas and kitchens,
unless the building is protected by an approved automatic sprinkler system
in accordance with 33.2.3.5 utilizing quick-response or residential sprinklers
throughout.
33.2.2.2.3
PROTECTION
K338
Interior Wall and Ceiling Finish
In Slow Evacuation Capability facilities, interior
wall an
d ceiling finish
materials in accordance with 10.2. Class A or C
lass B
is permitted. There
are no requirements for interior floor finish.
33.2.3.3.2, 33.2.3.3.3
K356
Sprinkler System – Supervisory Signals
In Slow Evacuation Capability facilities where an automatic sprinkler system
is installed, for either total or partial building coverage, the system shall be
in accordance with Section 9.7and shall initiate the fire alarm system in
accordance with 9.6, as modified below. The adequacy of the water supply
shall be documented.