Name of Facility
2012 LIFE SAFETY CODE
PART II – EXISTING RESIDENT BOARD & CARE OCCUPANCIES
MET
NOT
N/A
REMARKS
ID
MET
PREFIX
(PROMPT EVACUATION)
PROTECTION
K300
Protection – Other
List in the REMARKS section any LSC Section 33.2.3 Protection
requirements that are not addressed by the provided K-tags, but are
deficient. This information, along with the applicable Life Safety Code or
NFPA standard citation, should be included on Form CMS-2567.
K311
Vertical Openings – Enclosure
Vertical openings shall be protected so as not to expose a primary means of
escape. Vertical openings shall be considered protected if separated by
smoke partitions in accordance with 8.2.4 that resist the passage of smoke
from one story to any primary means of escape on another story. Smoke
partitions shall have a fire resistance rating on not less than 1/2 hour. Any
doors or openings to the vertical opening shall be capable of resisting fire for
not less than 20 minutes.
Stairs shall be permitted to be open where complying with sections
33.2.2.4.6 or 33.2.2.7.
33.2.3.1.1 through 33.2.3.1.4
Form CMS-2786V (10/2016)
Page
9