Name of Facility
2012 LIFE SAFETY CODE
PART II – EXISTING RESIDENT BOARD & CARE OCCUPANCIES
MET
NOT
N/A
REMARKS
ID
MET
PREFIX
(PROMPT EVACUATION)
K347
Smoke Alarms
Approved smoke alarms shall be provided in accordance with 9.6.2.10,
unless either of the following exist:
1. Buildings protected throughout by an approved automatic sprinkler
system, in accordance with 33.2.3.5, that uses quick response or
residential sprinklers, and protected with approved smoke alarms
installed in each sleeping room in accordance with 9.6.2.10, that are
powered by the building electrical system, or
2. Buildings are protected throughout by an approved automatic sprinkler
system, in accordance with 33.3.2.5, that uses quick-response or
residential sprinklers, with existing battery-powered smoke alarms in
each sleeping room, and where, in the opinion of the authority having
jurisdiction, the facility has demonstrated that testing, maintenance, and
a battery replacement program ensure the reliability of power to smoke
alarms.
Smoke alarms shall be installed on all levels, including basement but
excluding crawl spaces and unfinished attics. Additional smoke alarms shall
be installed for living rooms, dens, day rooms, and similar spaces. These
alarms shall be powered from the building electrical system and when
activated, shall initiate an alarm that is audible in all sleeping areas.
33.2.3.4.3
Form CMS-2786V (10/2016)
Page
12