Name of Facility
2012 LIFE SAFETY CODE
PART II – EXISTING RESIDENT BOARD & CARE OCCUPANCIES
ID
NOT
MET
N/A
REMARKS
PREFIX
MET
(IMPRACTICAL EVACUATION)
Automatic Sprinklers shall not be required in bathrooms not exceeding 55
K359
square feet, provided that such spaces are finished with lath and plaster or
materials provided a 15-minute thermal barrier.
In Impractical Evacuation Capability Facilities up to and including four
stories above grade plane, systems in accordance with NFPA 13R,
Standard for the Installation of Sprinkler Systems in Residential
Occupancies up to and Including Four Stories in Height, shall be permitted.
All habitable areas and closets shall be sprinklered. Automatic sprinklers
shall not be required in bathrooms not exceeding 55 square feet provided
that such spaces are finished with lath and plaster or materials providing a
15-minute thermal barrier.
Initiation of the fire alarm system shall not be required for existing
installations in accordance with 33.2.3.5.6.
Attics used for living purposes, storage, or fuel-fired equipment are sprinkler
protected. Attics not used for living purposes, storage, or fuel-fired
equipment meet one of the following:
1. Protected by heat detection system to activate the fire alarm system
according to 9.6.
2. Protected by automatic sprinkler system according to 9.7.
3. Constructed of noncombustible or limited-combustible construction; or
4. Constructed of fire-retardant-treated wood according to NFPA 703.
33.2.3.5.3, 33.2.3.5.3.2, 33.2.3.5.3.5 through33.2.3.5.3.7, 42 CFR
483.470(j)(1)(ii)
IF THE LEVEL OF EVACUATION DIFFICULTY IS IMPRACTICAL,
STOP HERE & CONTINUE TO PART IV AND PART V.
(ENSURE PROMPT, SLOW AND IMPRACTICAL SECTIONS ARE COMPLETE)
Form CMS-2786V (10/2016)
Page
23