Form Cms-2786v - Fire Safety Survey Report - Icf-Iid (Small Facilities) 2012 Life Safety Code Page 25

ADVERTISEMENT

 
 
Name of Facility
2012 LIFE SAFETY CODE
ID
NOT
PART III– NEW RESIDENTIAL BOARD & CARE OCCUPANCIES
MET
N/A
REMARKS
MET
PREFIX
K131
Multiple Occupancies – Sections of Residential Board and Care
Facilities
Multiple occupancies shall comply with 6.1.14.
No board and care occupancy shall have its sole means of escape pass
through any nonresidential or non-health care occupancy in the same
building.
No board and care occupancy shall be located above a nonresidential or
non-health care occupancy, unless one of the following are met:
1. The board and care occupancy and exits are separated by construction
having a minimum 2-hour fire resistance rating.
2. The nonresidential or non-health care occupancy is protected throughout
by an approved sprinkler system in accordance with 9.7 and is separated
by construction having a minimum 1-hour fire resistance rating.
32.1.3
K161
Building Construction Type and Height
In New Occupancies, there are no construction requirements.
MEANS OF ESCAPE REQUIREMENTS
K200
Means of Escape Requirements – Other
List in the REMARKS section any LSC Section 32.2.2 Means of Escape
requirements that are not addressed by the provided K-tags, but are
deficient. This information, along with the applicable Life Safety Code or
NFPA standard citation, should be included on Form CMS-2567.
K211
Means of Escape – General
Designated means of escape shall be continuously maintained clear of
obstructions or impediments to full instant use in the case of fire or
emergency.
32.2.2
Form CMS-2786V (10/2016)
Page
25