K351
Sprinkler System – Installation
All new occupancies shall be protected throughout by an approved,
supervised automatic sprinkler system in accordance with 32.2.3.5.3 using
quick response or residential sprinklers.
The system shall be in accordance with NFPA 13, Standard for the
Installation of Sprinkler Systems, and shall initiate the fire alarm system in
accordance with 9.6. The adequacy of the water supply shall be documented.
In new occupancies up to and including four stories above grade plane,
systems in accordance with NFPA 13R, Standard for the Installation of
Sprinkler Systems in Residential Occupancies up to and Including Four
Stories in Height, shall be permitted. All habitable areas, closets, roofed
porches, roofed decks, and roof balconies shall be sprinklered.
In new occupancies, an automatic sprinkler system in accordance with NFPA
13D, Standard for the Installation of Sprinkler Systems in One-and-Two-
Family Dwellings and Manufactured Homes, with a 30-minute water supply,
shall be permitted. All habitable areas, closets roofed porches, roofed decks,
and roof balconies shall be sprinklered.
Automatic sprinklers systems in accordance with NFPA 13 and 13R are
provided with electrical supervision in accordance with 9.7.2.
Automatic sprinkler systems in accordance with NFPA 13D shall be provided
with valve supervision by one of these methods:
1. Single listed control valve that shuts off both domestic and sprinkler
system, and separate shutoff for domestic system only.
2. Electrical supervision in accordance with 9.7.2.
3. Valve closure that caused the sounding of an audible signal in the facility
Attics used for living purposes, storage, or fuel-fired equipment are sprinkler
protected in accordance with 9.7.1.1.
Attics not used for living purposes, storage, or fuel-fired equipment meet one
of the following:
1. Protected by heat detection system to activate the fire alarm system
according to 9.6.
2. Protected by automatic sprinkler system according to 9.7.1.1.
3. Constructed of noncombustible or limited-combustible construction;
4. Constructed of fire-retardant-treated wood according to NFPA 703.
32.2.3.5.1, 32.2.3.5.3, 32.2.3.5.4, 32.2.3.5.5, 32.2.3.5.3.7