Name of Facility
2012 LIFE SAFETY CODE
PART II – EXISTING RESIDENT BOARD & CARE OCCUPANCIES
MET
NOT
N/A
REMARKS
ID
MET
PREFIX
(PROMPT EVACUATION)
K352
Sprinkler System – Supervisory Signals
Where a required automatic sprinkler system is installed, supervisory
attachments are installed and monitored for integrity in accordance with
NFPA 72, National Fire Alarm and Signaling Code, and provide a signal
that sounds and is displayed at a continuously attended location or
approved remote facility, when sprinkler operation is impaired.
An automatic sprinkler system in accordance with NFPA 13D would not
require water flow alarms where a facility has smoke alarms or smoke
detectors in accordance with NFPA 72.
9.7.2.1, 7.6 (NFPA 13D), NFPA 72
K353
Sprinkler System – Maintenance and Testing
NFPA 13 and 13R Systems
All sprinkler systems installed in accordance with NFPA 13, Standard for
the Installation of Sprinkler Systems, and NFPA 13R, Standard for the
Installation of Sprinkler Systems in Residential Occupancies Up To and
Including Four Stories in Height, are inspected, tested and maintained in
accordance with NFPA 25, Standard for Inspection, Testing and
Maintenance of Water Based Fire Protection System.
NFPA 13D Systems
Sprinkler systems installed in accordance with NFPA 13D “Standard for
the Installation of Sprinkler Systems in One – and Two – Family Dwellings
and Manufactured Homes” are inspected, tested and maintained in
accordance with the following requirements of NFPA 25:
1. Control valves inspected monthly (NFPA 25, section 13.3.2).
2. Gauges inspected monthly (NFPA 25, section 13.2.71).
3. Alarm devices inspected quarterly (NFPA 25, section 5.2.6).
4. Alarm devices tested semiannually (NFPA 25, section 5.3.3).
5. Valve supervisory switches tested semiannually (NFPA 25, section
13.3.3.5).
6. Visible sprinklers inspected annually ((NFPA 25, section 5.2.1).
7. Visible pipe inspected annually (NFPA 25, section 5.2.2).
8. Visible pipe hangers inspected annually (NFPA 25, section 5.2.3).
9. Buildings inspected annually prior to freezing weather for adequate
heat for water filled piping (NFPA 25, section 5.2.5).
10. A representative sample of fast response sprinklers are tested at 20
years (NFPA 25, section 5.3.1.1.1.2).
Form CMS-2786V (10/2016)
Page
14